AEMC 6555 15,000V Megohmmeter

The Megohmmeter Model 6555 is a high-end portable measuring instrument intended for the measurement of a wide variety of electrical insulation resistance values on cables and devices operating at high voltage. It is the only fully automated 15,000V graphical insulation tester. The True Megohmmeter® Model 6555 is packaged in a rugged case that is IP65 when closed. Test results and configuration information are displayed on a graphical LCD screen and are exportable via DataView® (provided). This megohmmeter can operate on battery or AC power.

The Model 6555 also offers the ability to program up to three step voltage profiles (from 40 to 15,000V), each containing up to ten steps. There are also three ramp profiles and three programmable test voltages in addition to the standard fixed voltages of 500, 1000, 2500, 5000, 10,000 and 15,000V.

Data Sheet

Description

 

Features

  • Detection and measurement of input voltage, frequency, and current prior  to running a test
  • Measurements at a fixed test voltage of 500, 1000, 2500, 5000, 10,000 or  15,000VDC
  • Measurements at an adjustable test voltage between 40 and 15,000VDC
  • Ramp voltage measurements with a ramp from 40 to 1100V or from 500 to  15,000V
  • Step voltage measurements with steps from 40 to 15,000V
  • Non-destructive (Early break) test, test stopped at a preset current  (Break at I-limit) or Burn mode with no predefined stop point
  • Digital filtering of insulation measurements
  • Live measurement of the voltage to warn the operator of potential unsafe  conditions
  • Programmable thresholds to trigger audible
  • Timed measurement duration checks
  • Fuse protection with display indication of defective fuse condition
  • Stores up to 80,000 measurements
  • Optically-isolated USB communication for transfer onto PC and and report generation with the included DataView® software
Applications

  • Acceptance testing and preventive maintenance
  • Test motors, pumps, valves, cables, switchgears  and electrical wiring installations
  • Continuity checks
  • High resistance or absorption tests
  • Spot  reading tests
  • Timed  resistance measurements
  • Dielectric  Absorption Ratio (DAR) and Polarization Index (PI)  tests
  • Multi-layer  insulation testing (DD)
  • Test old  or water damaged installations over long time periods
  • Motor  insulation resistance measurements